Place of Origin : CHINA
Brand Name : IUXPOWER
Certification : iso-9001
Model Number : ALB-SR/DR
MOQ : 1
Price : email
Packaging Details : BOX
Delivery Time : 15H
Payment Terms : T/T
Supply Ability : 100PCS
AC220V-6KW-R single-phase AC load bank
ALBDR6- AC220V-6KW-R single-phase AC load with pure resistive load; it can simulate all kinds of power load, meet the power unit, UPS power supply, inverter AC power full load detection is needed, production workshop, laboratory, installation and debugging, research and development necessary detection tools.
The main engine has temperature overheating automatic alarm protection function: due to special reasons, when overheating occurs, it can automatically cut off the load.
The whole machine is composed of resistive load. The load adopts energy dissipation method, and the heat dissipation adopts forced air cooling mode.
The fan adopts small axial flow fan, which has the characteristics of large air flow, good heat dissipation and low noise.
The above features make the whole machine better than imported products in safety, reliability and noise reduction.
In subsequent chapters, the components of the system will be introduced to help users understand the principles, functions and features of the system.
(1) safety of power supply reactors and similar products - Part 1: General requirements GB 19212.1-2008
(2) mechanical safety, machinery, electrical equipment, Part 1: General technical conditions, GB, 5226.1-2002
(3) general provisions on low-voltage switchgear and control equipment GB/T 14048.1-2000
(4) marine diesel generator set, GB/T 13032-2010
(5) general specification for military internal combustion engines, GJB 2815-97
(6) general specification for military mobile mobile loads GJB 235A-97
(7) general technical specifications for intermediate frequency mobile loads GJB 235-87
(8) general test method for load of military internal combustion engine. GJB 1488-93
(9) standards for the design of industrial enterprises GBZ1 - 2002
Three , main function and specification parameter
(1) rated input voltage: single phase 220V
(2) rated input power: 6KW
(3) power partition: 500W/500W/1KW/1KW/1KW/1KW/1KW (or custom defined)
(4) power factor: PF=1
(5) load accuracy: + 5%
(6) measuring accuracy: + 0.5%
(7) display mode: LED digital real-time display of load voltage and current (optional)
(8) power supply: AC single phase AC220V/50Hz
(9) control mode: panel manual control, sectional manual adjustable
(10) insulation grade: F class;
(11) protection grade: IP20 (suitable for indoor use)
(12) fan noise: 65 decibels
(13) cooling mode: forced air cooling: forward wind, rear wind
(14) working method: continuous work;
(15) protection function: over current protection, over temperature protection, over temperature alarm, beep prompt and so on
(16) external dimensions: host reference (wide *600, deep *482, high 180mm)
(17) use ambient temperature: -10, ~+50 centigrade
(18) mobile: Portable
(19) the use of relative humidity: less than 95%
(20): less than 2500 meters altitude
(21) atmospheric pressure: 86 ~ 106kPa;
![]() |